Arc-Resistant Switchgear: IEEE C37.20.7 Types and Suffixes
TL;DR
Arc-resistant switchgear per IEEE C37.20.7 is tested to contain and redirect the energy of an internal arcing fault — typically for a full 0.5 second (30 cycles) — venting pressure, molten metal, and plasma upward through a plenum instead of out the front of the cubicle. The standard defines accessibility Type 1 (front only) and Type 2 (all freely accessible sides), plus suffixes B, C, and D for what may be open during the event. Type 2B is the common data-center and industrial specification. It does not reduce incident energy — it redirects it while the equipment is closed and latched.
On this page
What arc-resistant construction does
An internal arcing fault in a medium-voltage enclosure releases enormous energy — pressure, molten metal, and plasma — in a fraction of a second. Arc-resistant switchgear per IEEE C37.20.7 is tested to contain and redirect that energy rather than let it blow out the front of the cubicle at the operator.
The tested performance is specific: the assembly must contain the fault typically for a full 0.5 second, 30 cycles, and vent the released energy upward through a plenum or duct — away from anyone standing in front of the gear. The point is worker protection during the moment of an internal fault, achieved structurally: heavier construction, latched doors, and a defined exhaust path.
This is the same class of medium-voltage switchgear covered elsewhere; arc-resistant is a construction option layered on top of the metal-clad or metal-enclosed choice, not a separate kind of gear.
Accessibility Types 1 and 2
IEEE C37.20.7 grades protection by where around the enclosure the operator is protected during an arcing fault:
- Type 1 protects only at the front of the equipment.
- Type 2 protects at all freely accessible sides — front, back, and sides.
Type 2 is the more comprehensive rating, and it is what most specifications default to for gear an operator can walk around. A line-up placed against a wall might be a candidate for Type 1, but where the equipment is free-standing and accessible on multiple sides, Type 2 is the honest match to how people actually work around it.
| Designation | Protection during an internal arcing fault |
|---|---|
| Type 1 | Front of the equipment only |
| Type 2 | All freely accessible sides (front, back, sides) |
| Suffix B | Protection maintained with the LV control/instrument compartment door open |
| Suffix C | Protection at the barrier between adjacent compartments |
| Suffix D | Protection at the door between compartments in the same cell |
The B, C, and D suffixes
The suffixes describe what may be open during the arcing event and still keep the protection valid:
- B adds protection with the low-voltage control or instrument compartment door open — the compartment an operator most often has open while working.
- C covers the barrier between adjacent compartments — protection is maintained across the divider to the next compartment.
- D covers the door between compartments in the same cell.
Type 2B is the common data-center and industrial specification. It combines all-sides protection with continued protection when the low-voltage compartment door is open, which matches how the gear is actually operated and maintained. The suffix stack is additive detail; get the type and the B suffix right first, then decide whether C or D is warranted for the specific arrangement.
Two things engineers get wrong
Arc-resistant construction earns its keep, but it is routinely oversold. Two caveats matter more than any marketing line:
- It does not reduce incident energy. Arc-resistant construction redirects the energy of an internal fault while the equipment is closed and latched to its tested configuration. Open a door outside that configuration and you are back to the full calculated incident energy and the PPE that goes with it. Arc-resistant gear is a complement to an arc-flash study, not a substitute for one.
- Venting is a building problem. The plenum has to discharge somewhere — overhead clearance, a roof penetration, or ducting to the outside. Discovering the venting requirement after the room is designed is expensive. The exhaust path belongs in the room layout from the start.
The genuine incident-energy reduction comes from clearing the fault faster, not from the enclosure: arc-flash relays that sense light plus overcurrent and trip in a few milliseconds, and maintenance-mode settings that temporarily remove intentional time delay while someone is working in front of the gear. Arc-resistant construction and fast clearing are complementary — the first protects during the fault, the second shortens it. Arc-resistant line-ups are available through Pantheon in the electrical catalog; the construction and voltage class are specified together.
Frequently asked questions
Does arc-resistant switchgear remove the need for arc-flash PPE?
No. Arc-resistant construction per IEEE C37.20.7 contains and redirects the energy of an internal fault while the equipment is closed and latched in its tested configuration. It does not lower the calculated incident energy at an open door. Real incident-energy reduction comes from faster clearing — arc-flash relaying and maintenance-mode settings — not from the enclosure.
What is the difference between Type 1 and Type 2 arc-resistant switchgear?
Type 1 protects the operator only at the front of the equipment during an internal arcing fault. Type 2 protects at all freely accessible sides — front, back, and sides. Type 2 is the more comprehensive rating and the usual choice for free-standing gear an operator can walk around.
What does the B in Type 2B mean?
The B suffix means protection is maintained with the low-voltage control or instrument compartment door open — the compartment operators most often have open while working. Type 2B combines all-sides (Type 2) protection with that open-door case, which is why it is the common data-center and industrial specification. The C and D suffixes extend protection to the barrier between adjacent compartments and the door between compartments in the same cell.
How long does arc-resistant switchgear contain a fault?
Typically a full 0.5 second — 30 cycles — under IEEE C37.20.7, venting the released pressure, molten metal, and plasma upward through a plenum or duct instead of out the front of the cubicle. The rating certifies containment for that tested duration while the equipment is closed and latched.
Why does arc-resistant switchgear need a plenum or duct?
Because the energy has to go somewhere. Arc-resistant construction redirects the arc blast upward and out through a plenum, which then needs overhead clearance, a roof penetration, or ducting to the outside. Venting is a building problem — the exhaust path must be planned into the room layout from the start, not discovered after the room is designed.
Related
Medium-voltage switchgear explained
Medium-voltage switchgear is the assembly of circuit breakers or switches, bus, instrument transformers, and protective relays that sectionalizes and protects a distribution system above 1000 V. The distinction that matters most is metal-clad (IEEE C37.20.2 — draw-out breakers, compartmentalized, interlocked) versus metal-enclosed (IEEE C37.20.3 — fused switches, far fewer structural requirements). All metal-clad gear is metal-enclosed; the reverse is not true, and a loosely written spec gets you the cheaper one.
Read →Metal-Clad vs Metal-Enclosed Switchgear
Metal-clad and metal-enclosed are two different IEEE standards, not two words for the same thing. Metal-clad switchgear (IEEE C37.20.2) has a defined structural recipe — draw-out breakers, grounded metal barriers between compartments, automatic shutters, insulated bus, and mechanical interlocks. Metal-enclosed interrupter switchgear (IEEE C37.20.3) is a performance standard that only requires a switch to safely interrupt load current inside a grounded enclosure. Every metal-clad line-up is metal-enclosed; most metal-enclosed line-ups are not metal-clad — and a loosely written spec gets you the cheaper one.
Read →4.16 kV, 13.8 kV, and 34.5 kV Switchgear: Which Voltage Class You Need
Switchgear is rated by a maximum voltage class, not by the nominal system voltage a buyer searches for. A 4.16 kV or 13.8 kV system both take 15 kV class gear; a 34.5 kV system takes 38 kV class. The preferred classes in IEEE C37.06 are 4.76, 8.25, 15, 27, and 38 kV, each with its own basic impulse level (BIL). Asking for "13.8 kV switchgear" is ambiguous; asking for "15 kV class, 95 kV BIL" is not.
Read →What is a unit substation?
A unit substation is a factory-coordinated assembly that takes medium-voltage service in one end and delivers usable distribution voltage out the other. It has three close-coupled sections — a primary (incoming) section, a step-down transformer, and a secondary switchgear or switchboard section. IEEE C37.121 covers three-phase step-down unit substations of 112.5 kVA and larger at primary voltages from 601 V through 52 kV.
Read →Last updated