PantheonGet Early Access

Metal-Clad vs Metal-Enclosed Switchgear

TL;DR

Metal-clad and metal-enclosed are two different IEEE standards, not two words for the same thing. Metal-clad switchgear (IEEE C37.20.2) has a defined structural recipe — draw-out breakers, grounded metal barriers between compartments, automatic shutters, insulated bus, and mechanical interlocks. Metal-enclosed interrupter switchgear (IEEE C37.20.3) is a performance standard that only requires a switch to safely interrupt load current inside a grounded enclosure. Every metal-clad line-up is metal-enclosed; most metal-enclosed line-ups are not metal-clad — and a loosely written spec gets you the cheaper one.

On this page

Two standards, not two words

In the field "metal-clad" and "metal-enclosed" get used as if they were interchangeable. They are not — they name different IEEE standards with different requirements, and the gap between them is the whole point of this page.

  • Metal-clad switchgear is built to IEEE C37.20.2. This is a construction standard: it dictates a specific physical recipe the assembly must follow.
  • Metal-enclosed interrupter switchgear is built to IEEE C37.20.3. This is a performance standard: it says what the switch must accomplish, and leaves most of the construction open.
  • Metal-enclosed low-voltage power circuit-breaker switchgear is a third, separate standard, IEEE C37.20.1 — the low-voltage cousin, out of scope for a medium-voltage line-up but often confused into the same conversation.

"Metal-enclosed" is the umbrella: it means the live parts sit inside a grounded metal box. "Metal-clad" is a specific, heavily-specified kind of metal-enclosed gear. This is the medium-voltage switchgear distinction that costs the most money to get wrong.

What metal-clad (IEEE C37.20.2) actually requires

Metal-clad construction is defined by a checklist. To earn the label, a line-up must have all of the following:

  • Draw-out (removable) circuit breakers — the breaker rolls out of its cell rather than being fixed-mounted.
  • Grounded metal barriers separating every major compartment from the others: breaker, main bus, cable, and instrumentation each sit in their own grounded metal box.
  • Automatic shutters that cover the primary stabs — the live connection points — whenever the breaker is racked out, so an open cell does not expose energized metal.
  • Insulated primary bus — the main bus is insulated, not bare.
  • Mechanical interlocks that prevent racking a closed breaker into or out of its connected position.

Every one of those is a safety and maintainability feature. Together they are what let you open a feeder, rack that breaker out behind closed shutters, and work on it while the main bus and every other feeder stay energized.

RequirementMetal-clad (C37.20.2)Metal-enclosed interrupter (C37.20.3)
Standard typeConstruction (prescriptive recipe)Performance (what it must do)
Switching elementDraw-out circuit breakerFixed or fused load-interrupter switch
Compartment barriersRequired — grounded metal between all compartmentsNot required
Automatic shutters over stabsRequiredNot required
Insulated primary busRequiredNot required
Mechanical interlocksRequiredNot required
Service a device while bus is liveYes — rack out behind closed shuttersOften means de-energizing the assembly

What metal-enclosed interrupter (IEEE C37.20.3) requires

Metal-enclosed interrupter switchgear asks for far less. The standard is a performance requirement: the switch must safely interrupt load current inside a grounded enclosure. That is essentially the whole demand.

It does not require draw-out elements, full compartmentalization, automatic shutters, insulated bus, or the metal-clad interlock scheme. A typical metal-enclosed line-up uses fixed-mounted, fused load-interrupter switches: compact, mechanically simple, and cheaper. The trade is operational. With fixed-mounted or fused gear, servicing one device often means de-energizing the whole assembly, because there is no draw-out mechanism and no shutter to isolate a single cell while the rest stays live.

Neither approach is "wrong." A metal-enclosed interrupter line-up is proportionate for smaller, non-critical, or seldom-touched loads. It is only wrong when it is specified for a job that assumed metal-clad capability.

Why the wrong word costs money

Here is the failure mode the standards exist to prevent. "Metal-enclosed" is the superset — every metal-clad line-up is metal-enclosed, but not the reverse. So a specification that simply says "metal-enclosed switchgear" is technically satisfied by the cheaper C37.20.3 gear, even if the one-line drawing assumes draw-out breakers, relay coordination, and the ability to maintain a feeder live.

That mismatch is a real and common defect: the design intends metal-clad capability, the words permit metal-enclosed, and the low bidder supplies exactly what the words allowed. The fix is one sentence. Write "metal-clad per IEEE C37.20.2" whenever the design needs draw-out breakers, compartmentalization, or live maintainability — and reserve "metal-enclosed per IEEE C37.20.3" for line-ups where a fixed or fused switch is genuinely enough.

The construction choice also interacts with the voltage class you need and with whether the line-up is arc-resistant — but the metal-clad-versus-metal-enclosed decision is the one that most often ships wrong. Metal-clad line-ups are available through Pantheon in the electrical catalog.

Frequently asked questions

Is metal-clad switchgear the same as metal-enclosed switchgear?

No. Metal-clad is a subset. IEEE C37.20.2 metal-clad construction requires draw-out breakers, grounded metal barriers between compartments, automatic shutters, insulated primary bus, and mechanical interlocks. IEEE C37.20.3 metal-enclosed interrupter switchgear only requires that a switch safely interrupt load current inside a grounded enclosure. Every metal-clad line-up is metal-enclosed; most metal-enclosed line-ups are not metal-clad.

What is medium voltage metal-enclosed switchgear?

It is a line-up built to IEEE C37.20.3 — a grounded metal enclosure around a switch (usually a fixed-mounted, fused load-interrupter switch) rated to safely interrupt load current, for medium-voltage systems above 1000 V. It omits the draw-out breakers, compartment barriers, shutters, and interlocks that metal-clad construction (C37.20.2) requires, which makes it simpler and cheaper but generally means de-energizing the assembly to service a device.

Which IEEE standard covers metal-clad switchgear?

IEEE C37.20.2. Metal-enclosed interrupter switchgear is C37.20.3, and metal-enclosed low-voltage power circuit-breaker switchgear is C37.20.1 — three distinct standards that are frequently confused because the words overlap.

Can you service metal-enclosed switchgear while it is energized?

Usually not one device at a time. Metal-enclosed interrupter switchgear typically uses fixed-mounted or fused switches with no draw-out mechanism and no automatic shutters, so servicing a device often means de-energizing the whole assembly. Metal-clad gear is what lets you rack one breaker out behind closed shutters and work on it while the main bus and other feeders stay live.

When should a specification call for metal-clad instead of metal-enclosed?

Whenever the design needs draw-out breakers, relay-based coordination with settable curves, or the ability to maintain a feeder while the rest of the line-up stays energized — the critical-path feeds in a data center, for example. A fused metal-enclosed line-up is proportionate for smaller, non-critical, or seldom-touched loads. State the standard explicitly: "metal-clad per IEEE C37.20.2."

Related

Medium-voltage switchgear explained

Medium-voltage switchgear is the assembly of circuit breakers or switches, bus, instrument transformers, and protective relays that sectionalizes and protects a distribution system above 1000 V. The distinction that matters most is metal-clad (IEEE C37.20.2 — draw-out breakers, compartmentalized, interlocked) versus metal-enclosed (IEEE C37.20.3 — fused switches, far fewer structural requirements). All metal-clad gear is metal-enclosed; the reverse is not true, and a loosely written spec gets you the cheaper one.

Read →

4.16 kV, 13.8 kV, and 34.5 kV Switchgear: Which Voltage Class You Need

Switchgear is rated by a maximum voltage class, not by the nominal system voltage a buyer searches for. A 4.16 kV or 13.8 kV system both take 15 kV class gear; a 34.5 kV system takes 38 kV class. The preferred classes in IEEE C37.06 are 4.76, 8.25, 15, 27, and 38 kV, each with its own basic impulse level (BIL). Asking for "13.8 kV switchgear" is ambiguous; asking for "15 kV class, 95 kV BIL" is not.

Read →

Arc-Resistant Switchgear: IEEE C37.20.7 Types and Suffixes

Arc-resistant switchgear per IEEE C37.20.7 is tested to contain and redirect the energy of an internal arcing fault — typically for a full 0.5 second (30 cycles) — venting pressure, molten metal, and plasma upward through a plenum instead of out the front of the cubicle. The standard defines accessibility Type 1 (front only) and Type 2 (all freely accessible sides), plus suffixes B, C, and D for what may be open during the event. Type 2B is the common data-center and industrial specification. It does not reduce incident energy — it redirects it while the equipment is closed and latched.

Read →

What is a unit substation?

A unit substation is a factory-coordinated assembly that takes medium-voltage service in one end and delivers usable distribution voltage out the other. It has three close-coupled sections — a primary (incoming) section, a step-down transformer, and a secondary switchgear or switchboard section. IEEE C37.121 covers three-phase step-down unit substations of 112.5 kVA and larger at primary voltages from 601 V through 52 kV.

Read →

Share this page

Last updated