GE Vernova
GE LM6000 PD SPRINT (DLE) Cogeneration Plant — 46–48 MW + 50–55 t/h HRSG
Used and surplus GE LM6000 PD SPRINT DLE cogeneration plant for sale — a complete 46–48 MW combined-heat-and-power block with a 50–55 t/h heat-recovery steam generator, an exchanged factory-refurbished engine at 28,000–32,000 hours, measured performance and accredited emissions data.
Used and surplus GE LM6000 PD SPRINT cogeneration plant with Dry Low Emissions (DLE) combustion available for sale through Pantheon — a complete plant rather than a bare generating set. The scope comprises the LM6000 PD SPRINT gas turbine, generator and load gearbox, a heat-recovery steam generator rated at 50–55 tonnes per hour of high-pressure steam, natural-gas booster compression, a distributed control system with modern turbine controls and vibration monitoring, generator switchgear, and a spares inventory included in the sale. The plant was commissioned in 2010–2013; in 2020–2022 the complete engine was exchanged for a factory-refurbished unit, documented in an OEM removal-and-installation report, and that engine now carries 28,000–32,000 hours. Per OEM guidance the next major event falls at 50,000 engine hours — about 20,000 hours of runway — and is a hot-section exchange with a minor generator inspection, not a full major overhaul. The headline package hours are far higher; the engine figure is the one that describes remaining life. Performance is measured, not asserted: an OEM test-cell report after that engine’s overhaul recorded corrected sprinted gross output of 46–47 MW at a heat rate of 8,400–8,700 Btu/kWh, within guarantee tolerance, and an independent accredited stack test from the last 18 months returned NOx and CO comfortably inside consent against a ≤25 ppmvd design basis — useful documents for a buyer facing a permitting process. Three open items from the most recent inspection — one hot-section follow-up and two component replacements — are disclosed in full at quote; one booster compressor is high-hours and should be treated as a replacement item; the OEM service agreement has lapsed and a buyer would negotiate a new one. The plant was laid up in 2024–2025 and is stored to OEM recommendation. Dismantling and export from site is a substantial exercise and should be scoped early. Exact rating, hours, and configuration confirmed at quote.
Specifications
| Type | Complete cogeneration plant · LM6000 PD SPRINT aeroderivative gas turbine |
|---|---|
| Output (electrical) | 46–48 MW nameplate · 46–47 MW corrected sprinted gross on OEM test cell |
| Heat rate (measured) | 8,400–8,700 Btu/kWh on OEM test cell, within guarantee tolerance |
| Steam | HRSG rated 50–55 t/h high-pressure steam |
| Combustor | DLE (dry low emissions) · design basis ≤25 ppmvd NOx and CO at 15% O₂ |
| Emissions (measured) | Independent accredited stack test within the last 18 months · NOx and CO well inside consent limits |
| SPRINT | Spray intercooling · holds rated output on hot days |
| Balance of plant | Generator · load gearbox · gas booster compression · DCS · vibration monitoring · switchgear · spares |
| Fuel | Natural gas |
| Engine history | Plant commissioned 2010–2013 · complete engine exchanged 2020–2022 for a factory-refurbished unit |
| Operating hours | 28,000–32,000 engine hours · next major event at 50,000 h is a hot-section exchange, not a major overhaul |
| Documentation | OEM engine-exchange report · test-cell performance · borescope + semi-annual inspections · controls, compressor-cleaning and emissions reports · spares inventory · lifting and shipping drawings |
| Open items | Three from the latest inspection (one hot-section follow-up, two component replacements) · one high-hours booster compressor — full list at quote |
| Delivery | On order placement · dismantling and export to be scoped early |
| Offer window | Lot listed through 2026-12-31 · availability re-confirmed at quote |
| Condition | Used and surplus · laid up 2024–2025, stored to OEM recommendation |
Specifications shown are headline figures. Confirm full configuration details when you request a quote.
Last updated
Request a quote for GE LM6000 PD SPRINT DLE Cogeneration Plant
Tell us your requirements and we'll get back to you with availability and pricing.
or reach us directly at